When you click on links to various merchants on this site and make a purchase, this can result in this site earning a commission. Affiliate programs and affiliations include, but are not limited to, the eBay Partner Network.
Fisher 61 Series Pilots are used with the Type 1098-EGR and EZL regulators and their counterparts are used with 99 Series regulators. Available in a variety of styles - low pressure (L), low pressure and wide proportional band (LE), low pressure and narrow proportional band (LD), high pressure (H) and extra high pressure (HP). Pilot-operated regulators use inlet pressure as the operating medium, which is reduced through pilot operation to load the actuator Constructions: Type 61L: Low-Press Pilot Type 61LD: Low-Press Pilot w/Narrowing Proportional Band Type 61LE: Low-Press Pilot w/Broadened Proportional Band Type 61H: High-Press Pilot Type 61HP: Extra High-Press Pilot
Maximum Inlet Pressure: Types 61L, 61LE, and 61H: 300 psig / 20,7 bar || Type 61LD: 160 psig / 11,0 bar || Type 61HP: 600 psig / 41,4 bar
Outlet Pressure Registration: 0 to 300 psig / 0 to 20,7 bar
Maximum Spring Case Pressure for Pressure Loading: Types 61L, 61LD, and 61LE: 25 psig / 1,7 bar || Type 61H: 72 psig / 5,0 bar || Type 61HP: 100 psig / 6,9 bar
Material Temperature Capabilities: Standard Elastomers: -20° -150°F / -29°-66°C || High-Temp Elastomers: 0°-300°F/-18°-149°C, except 0°-200°F/-18° to 93°C for water service
Pressure Connection1/4 NPT